XLPE insulated power cable for rated voltage up to and including 35kV

XLPE insulated power cable for rated voltage up to and including 35kV IEC 60502 GB/T 12706 is for power transmission in power plant & electric power circuit

Application

This product applies for power transmission in power plant and electric power circuit of rated voltage up to and including 35kV. XLPE insulated power cable has outstanding mechanical property, excellent electrical and anti-corrosion properties. It has other advantages, such as it is hight and convenient for transportation and laying, and not restricted for height difference. Thus it is widely used in metal refining, electric power, petro-chem enterprises and urban network construction etc.

Executive Standard

GB/T 12706 (equivalently adopt IEC 60502 standard)

Service Property

Service PropertyXLPE insulation
Rated voltage (kV)0.6/1、1.8/3、3.6/6、6/6、6/10、8.7/10、8.7/15、12/20、18/20、18/30、21/35、26/35
Maximum operating temperature of conductor90℃
Short circuit temperature (lasting no longer than 5 seconds)≤250℃
Ambient temperature for laying≥0℃(Preheated when lower than 0℃)
Allowed bending radius for layingSingle core non-armored cable≥20 times the outer diameter of the cable
Single core armored cable≥15 times the outer diameter of the cable
Multicore non-armored cable≥15 times the outer diameter of the cable
Multicore armored cable≥12 times the outer diameter of the cable
Flame retardant propertyConform to GB/T 18380.33-35 flame test on bunched wires or cables

Type & Description

TypeDescription
YJV、YJLVCopper or aluminum core XLPE insulated PVC sheathed power cable
YJY、YJLYCopper or aluminum core XLPE insulated PE sheathed power cable
YJV22、YJLV22Copper or aluminum core XL PE insulated steel tape armored PVC sheathed power cable
YJV23、YJLV23Copper or aluminum core XLPE insulated steel tape armored PE sheathed power cable
YJV24、YJLV24Copper or aluminum core X PE insulated steel tape armored elastomer sheathed power cable
YJV32、YILV32Copper or aluminum core XL PE insulated thin steel wire armored PVC sheathed power cable
YJV33、YJLV33Copper or aluminum core XLPE insulated thin steel wire armored PE sheathed power cable
YJV34、YILV34Copper or aluminum core XLPE insulated thin steel wire armored elastomer sheathed power cable
YJV42、YJLV42Copper or aluminum core XLPE insulated thick steel wire armored PVC sheathed power cable
YJV43、YJLV43Copper or aluminum core XLPE insulated thick steel wire armored PE sheathed power cable
YJV44、YJLV44Copper or aluminum core XLPE insulated thick steel wire armored elastomer sheathed power cable
YJV62、YJLV62Copper or aluminum core XLPE insulated non-magnetic metal tape armored PVC sheathed power cable
YJV63、YJLV63Copper or aluminum core Xl PE, insulated non-magnetic metal tape armored PE sheathed power cable
YJV64、YJLV64Copper or aluminum core Xl PE insulated non-magnetic metal tape armored elastomer sheathed power cable
YJV72、YJLV72copper or aluminum core X PE insulated non-magnetic metal wire armored PVC sheathed power cable
YJV73、YJLV73Copper or aluminum core XLPE, insulated non-magnetic metal wire armored PE sheathed power cable
YJV74、YJLV74Copper or aluminum core XL PE insulated non-magnetic metal wire armored elastomer sheathed power cable
ZA(B,C)-YJV
ZA(B,C)-YJLV
Copper or aluminum core XLPE insulated PVC sheathed flame retardant power cable
ZA(B,C)-YJY      ZA(B,C)-YJLYCopper or aluminum core X PE insulated polyolefin sheathed flame retardant power cable
ZA(B,C)-YJV22  ZA(B,C)-YJLV22Copper or aluminum core XLPE insulated steel tape armored PVC sheathed flame retardant power cable
ZA(B,C)-YJV23  ZA(B,C)-YJLV23Copper or aluminum core XL PE insulated steel tape armored polvolefin sheathed flame retardant power cable
ZA(B,C)-YJV32  ZA(B,C)-YJLV32Copper or aluminum core XLPE insulated thin steel wire armored PVC sheathed flame retardant power cable
ZA(B,C)-YJV33  ZA(B,C)-YJLV33Copper or aluminum core XLPE insulated thin steel wire armored polyolefin sheathed flame retardant power cable
ZA(B,C)-YJV42  ZA(B,C)-YJLV42Copper or aluminum core XLPE insulated thick steel wire armored PVC sheathed flame retardant power cable
ZA(B,C)-YJV43  ZA(B,C)-YJLV43Copper or aluminum core XLPE insulated thick steel wire armored polyolefin sheathed flame retardant power cable
ZA(B,C)-YJV62  ZA(B,C)-YJLV62Copper or aluminum core X PE insulated non-magnetic metal tape armored PVC sheathed flame retardant power cable
ZA(B,C)-YJV63  ZA(B,C)-YJLV63Copper or aluminum core XLPE insulated non-magnetic metal tape armored polyolefin sheathed flame retardant power cable
ZA(B,C)-YJV72  ZA(B,C)-YJLV72Copper or aluminum core XLPE insulated non-magnetic metal wire armored PVC sheathed flame retardant power cable
ZA(B,C)-YJV73  ZA(B,C)-YJLV73Copper or aluminum core XLPE insulated non-magnetic metal wire armored polyolefin sheathed flame retardant power cable
WDZA(B,C)-YJE WDZA(B,C)-YJLE WDZA(B,C)-YJYCopper or aluminum core X PE insulated polyolefin sheathed low smoke halogen free flame retardant power cable
WDZA(B,C)-YJE23 WDZA(B,C)-YJLE23 WDZA(B,C)-YJY23Copper or aluminum core XLPE insulated steel tape armored polyolefin sheathed low smoke halogen free flame retardant power cable
WDZA(B,C)-YJE33 WDZA(B,C)-YJLE33 WDZA(B,C)-YJY33Copper or aluminum core XLPE insulated thin steel wire armored polyolefin sheathed low smoke halogen free flame retardant power cable
WDZA(B,C)-YJE43 WDZA(B,C)-YJLE43 WDZA(B,C)-YJY43Copper or aluminum core XLPE insulated thick steel wire armored polyolefin sheathed low smoke halogen free flame retardant power cable
WDZA(B,C)-YJE63 WDZA(B,C)-YJLE63 WDZA(B,C)-YJY63Copper or aluminum core XLPE insulated non-magnetic metal tape anmored polyolefin sheathed low smoke halogen free flame retardant power cable
WDZA(B,C)-YJE73 WDZA(B,C)-YJLE73 WDZA(B,C)-YJY73Copper or aluminum core XLPE insulated non-magnetic metal wire armored polyolefin sheathed low smoke halogen free flame retardant power cable
DDZA(B,C)-YJV DDZA(B,C)-YJLVCopper or aluminum core XLPE insulated PVC sheathed low smoke low halogen flame retardant power cable
DDZA(B,C)-YJV22 DDZA(B,C)-YJLV22Copper or aluminum core XPE insulated steel tape armored PVC sheathed low smoke low halogen flame retardant power cable
DDZA(B,C)-YJV32 DDZA(B,C)-YJLV32Copper or aluminum core XLPE insulated thin steel wire armored PVC sheathed low smoke low halogen flameretardant power cable
DDZA(B,C)-YJV42 DDZA(B,C)-YJLV42Copper or aluminum core XL PE, insulated PVC sheathed low smoke low halogen flame retardant power cable
DDZA(B,C)-YJV62 DDZA(B,C)-YJLV62Copper or aluminum core XLPE insulated non-magnetic metal tape armored PVC sheathed low smoke low halogen flame retardant power cable
DDZA(B,C)-YJV72 DDZA(B,C)-YJLV72Copper or aluminum core XLPE, insulated non-magnetic metal wire armored PVC sheathed low smoke low halogen flame retardant power cable

Code & Meaning

ItemCodeDescription
Burning characteristic-Non flame retardant
Z (A/B/C)Flame retardant grade (A/B/C)
NFire resistant
WDZLow smoke halogen free flame retardant
DDZLow smoke low halogen flame retardant
InsulationYJXLPE
Conductor-Class 1 and 2 copper conductor
RClass 5 copper conductor
LAluminum conductor
ShieldSCopper wire winded sparsely
Sheath and inner sheathVPVC
YPolyolefin or polyethylene
ELows moke halogen free polyolefin
Armor2Galvanized steel tape armor
3Thin steel wire armor
4Thick steel wire armor
6aNon-magnetic metal tape armor
7bNon-magnetic metal wire armor
Outer sheath2PVC sheath
3Polyolefin or polyethylene sheath
4Elastomer sheath

Main technical index

1. Conductor D.C.resistance at 20℃ should comply with GB/T3956.
2. Power frequency voltage test: withstand 2.5U0+2kV for 5 minutes without puncture for cables of rated voltage up to and including 1 .8kV; withstand 3.5U0 for 5 minutes without puncture for cables of rated voltage up to and including 3 .6kV.
3. Partial discharge test: discharge should not be detected when cable sensitivity is equal or superior to 10pC for cables of rated voltage Uo is 3.6kV and above.

Cable specification and structural parameter

TypeRated voltage(kV)
CuAlNumber of cores0.6/11.8/33.6/66/6 6/108.7/10 8.7/1512/2018/3021/3526/35
YJV、YJY  ZA(B,C)-YJV WDZA(B,C)-YJE WDZA(B,C)-YJY DDZA(B,C)-YJVYJLV、YJLY ZA(B,C)-YJLV WDZA(B,C)-YJLE WDZA(B,C)-YJLY DDZA(B,C)-YJLV11.5-63010-63010-63016-63025-63035-63050-63050-63050-630
2、51.5-18510-300-------
31.5-30010-30010-30016-30025-30035-30050-30050-30050-300
41.5-30010-300-------
3+1、3+2、4+14-30010-300-------
YJV22、 YJV74 ZA(B,C)-YJV22 ZA(B,C)-YJV73 WDZA(B,C)-YJE23 WDZA(B,C)-YJE73 WDZA(B,C)-YJY23 WDZA(B.C)-YJY73 DDZA(B,C)-YJV22 DDZA(B,C)-YJV72YJLV22、 YJLV74 ZA(B,C)-YJLV22 ZA(B,C)-YJLV73 WDZA(B,C)-YJLE23 WDZA(B,C)-YJLE73 WDZA(B,C)-YJLY23 WDZA(B.C)-YJLY73 DDZA(B,C)-YJLV22 DDZA(B,C)-YJLV721---------
24-185--------
54-185--------
34-300-10-30016-30025-30035-30050-30050-30050-300
44-300--------
3+14-300--------
3+24-300--------
4+14-300--------