Fluoroplastics insulated heat resistant power cable 0.6/1kV

Fluoroplastics insulated heat resistant power cable 0.6/1kV applies for power transmission. High temperature, oil, acid & akali, corrosive gas resistant

Application
This product applies for power transmission of rated voltage up to and including 0.6/lkV, The product has the characteristics of high temperature resistant, oil resistant, acid and alkali resistant, corrosive gas resistant, waterproof and so on. Cable electrical properties arstable at high environment temperatures, has excellent aging resistant property, and long service life. Thus it is widely used in metallurgelectric power, petrochemical, electronics and automobile industry etc.

Executive Standard
Q/WHY 04

Service property
1. The rated voltage U0/U of the cable should be 0.6/1kV.
2. Maximum operating temperature: should be no more than 200℃ for F46 insulation; should be no more than 260℃ for PFAinsulation.
3. Minimum ambient temperature of fuoroplastic and silicon rubber sheath: Should be -60℃ for fixed laying, -15℃ for non fixed laying.
4. Cable laying temperature should be not less than 0℃ (not less than -25℃ for fuoroplastic and silicon sheath).
5. Allowed bending radius of single core cable should be not less than 10 times outer diameter of the cable, of multi-core cable should be not less than 15 times outer diameter of the cable.

Type & Description

Type Description
FF Fluoroplastic insulated and sheathed power cable
FFR Fluoroplastic insulated and sheathed flexible power cable
FFP Fluoroplastic insulated and sheathed copper wire braided shielded power cable
FFRP Fluoroplastic insulated and sheathed copper wire braided shielded flexible power cable
FV Fluoroplastic insulated PVC sheathed power cable
FV22 Fluoroplastic insulated steel tape armored PVC sheathed power cable
FV32 Fluoroplastic insulated steel wire armored PVC sheathed power cable
FG Fluoroplastic insulated silicon rubber sheathed power cable
FG24 Fluoroplastic insulated steel tape armored silicon rubber sheathed power cable
FG34 Fluoroplastic insulated steel wire armored silicon rubber sheathed power cable

Note: The type not listed in the table should be comprised according to following type explanation.

Code & Meaning

Item Code Description
Series coding Y Movable flexible cable
Burning characteristic Z(A/B/C) Flame retardant grade (A/B/C)
N Fire resistant
Insulation F Fluoroplastic insulation
Conductor Class 1 and 2 copper conductor
R Class 5 copper conductor
L Aluminum conductor
Shield P Copper wire braided shield
P2 Copper tape wrapped shield
P3 Aluminum plastic composite tape wrapped shield
Sheath F Fluoroplastic sheath
V PVC sheath
G Silicon rubber sheath
Armor layer 2 Steel tape armor
3 Steel wire armor
9 Galvanized steel wire braided armor
Outer sheath 2 105℃ PVC sheath
4 Silicon rubber sheath

Main technical index
1. Conductor D.C. resistance at 20℃ complies with stipulations of GB/T3956.
2. Insulation resistance at 20℃ should be not less than 500MΩ .km
3. Cable withstand A.C. 3.5kV for 5 minutes without puncture.

Structure diagram

RELATED PRODUCTS

GET IN TOUCH

We look forward to serving you! Our team will get back to you promptly.