0.6/1kV flame retardant B1 class power cable

0.6/1kV flame retardant B1 class power cable is applies for densely populated places, transmission and distribution lines, power transmission

Application

This product is suitable for ac rated voltage 0.6/1kV and below in densely populated places, transmission and distribution lines, power transmission, with high flame retardant,low smoke, halogen-free and other characteristics, large load flow, excellent anti-aging performance, long service life, this product has been widely used in metallurgy, electric power, petrochemical, large construction, automobile manufacturing and other industries.

Executive Standard

Q/WHY 92、GB/T 31247-2014

Service Property

1. In continuous operation, the highest operating temperature of the conductor is 90℃, and the laying temperature should not be lower than 0℃.
2. Rated voltage of cable 0.6/1kV.
3. Allowable bending radius: single core cable should not be less than 10 times of the cable diameter, multi core cable should not be less than 15 times of the cable diameter.

Type & Description

TypeDescription
WDZB1-YJYCopper core crosslinked polyethylene insulated low smoke halogen-free polyolefin sheathed flame retardant class 1 power cable
WDZB1-YJY23Copper core crosslinked polyethylene insulated galvanized steel tape armored low smoke halogen-free polyolefin sheathed flame retardant class 1 power cable
WDZB1-YJY33Copper core crosslinked polyethylene insulated galvanized steel wire armored low smoke halogen-free polyolefin sheathed flame retardant class 1 power cable

Code & Meaning

ItemCodeDescription
Series of codes/Omitted
Burning characteristicsB1Flame retardant class 1 cable
NCabinet
WDLow smoke
ZSingle flame retardant
Conductor/Copper conductor (omitted)
LAluminum conductor
LHAluminum alloy conductor
RSoft structure
InsulationYJCrosslinked polyethylene insulation
Sheath and inner sheathYLow smoke halogen-free polyolefin sheath
Armor2Double steel tape armmor
3Fine steel armor
4Thick steel armor
6Non-magnetic metal tape armor
7Non-magnetic metal wire armor
Outer Sheath3Low smoke halogen-free polyolefin sheath

Main Technical Indicators

1. DC resistance of conductor at 20℃ shall conform to GB/T3956-2008.
2. The power-frequency AC voltage test is 3.5kV/5min without breakdown.
3. The highest operating temperature of the conductor is 90℃.

Combustion performance index

ProjectIndex
Flame spreadFS≤1.5m
Peak heat release rateHRR (peak)≤30kW
Total heat release within 1200s by fireTHR1200≤15MJ
Combustion rate exponentialFIGRA≤150W/s
Peak smoke rateSPR(peak)≤0.25㎡/s
Total amount of smoke produced within 1200s by fireTSP1200≤50MJ
Smoke density(minimum transmittance)It≥60%
Vertical fame spreadH≤425mm
No combustion drips/particles within 1200sNo burning drips/particles
Smoke toxicityZA2
Electrical conductivity≤2.5 μ s/mm
PH≥4.3

Cable Structure drawing

RELATED PRODUCTS

GET IN TOUCH

We look forward to serving you! Our team will get back to you promptly.