0.6/1kV flame retardant B1 class power cable
0.6/1kV flame retardant B1 class power cable is applies for densely populated places, transmission and distribution lines, power transmission
Application
This product is suitable for ac rated voltage 0.6/1kV and below in densely populated places, transmission and distribution lines, power transmission, with high flame retardant,low smoke, halogen-free and other characteristics, large load flow, excellent anti-aging performance, long service life, this product has been widely used in metallurgy, electric power, petrochemical, large construction, automobile manufacturing and other industries.
Executive Standard
Q/WHY 92、GB/T 31247-2014
Service Property
1. In continuous operation, the highest operating temperature of the conductor is 90℃, and the laying temperature should not be lower than 0℃.
2. Rated voltage of cable 0.6/1kV.
3. Allowable bending radius: single core cable should not be less than 10 times of the cable diameter, multi core cable should not be less than 15 times of the cable diameter.
Type & Description
Type | Description |
---|---|
WDZB1-YJY | Copper core crosslinked polyethylene insulated low smoke halogen-free polyolefin sheathed flame retardant class 1 power cable |
WDZB1-YJY23 | Copper core crosslinked polyethylene insulated galvanized steel tape armored low smoke halogen-free polyolefin sheathed flame retardant class 1 power cable |
WDZB1-YJY33 | Copper core crosslinked polyethylene insulated galvanized steel wire armored low smoke halogen-free polyolefin sheathed flame retardant class 1 power cable |
Code & Meaning
Item | Code | Description |
---|---|---|
Series of codes | / | Omitted |
Burning characteristics | B1 | Flame retardant class 1 cable |
N | Cabinet | |
WD | Low smoke | |
Z | Single flame retardant | |
Conductor | / | Copper conductor (omitted) |
L | Aluminum conductor | |
LH | Aluminum alloy conductor | |
R | Soft structure | |
Insulation | YJ | Crosslinked polyethylene insulation |
Sheath and inner sheath | Y | Low smoke halogen-free polyolefin sheath |
Armor | 2 | Double steel tape armmor |
3 | Fine steel armor | |
4 | Thick steel armor | |
6 | Non-magnetic metal tape armor | |
7 | Non-magnetic metal wire armor | |
Outer Sheath | 3 | Low smoke halogen-free polyolefin sheath |
Main Technical Indicators
1. DC resistance of conductor at 20℃ shall conform to GB/T3956-2008.
2. The power-frequency AC voltage test is 3.5kV/5min without breakdown.
3. The highest operating temperature of the conductor is 90℃.
Combustion performance index
Project | Index |
---|---|
Flame spread | FS≤1.5m |
Peak heat release rate | HRR (peak)≤30kW |
Total heat release within 1200s by fire | THR1200≤15MJ |
Combustion rate exponential | FIGRA≤150W/s |
Peak smoke rate | SPR(peak)≤0.25㎡/s |
Total amount of smoke produced within 1200s by fire | TSP1200≤50MJ |
Smoke density(minimum transmittance) | It≥60% |
Vertical fame spread | H≤425mm |
No combustion drips/particles within 1200s | No burning drips/particles |
Smoke toxicity | ZA2 |
Electrical conductivity | ≤2.5 μ s/mm |
PH | ≥4.3 |
Cable Structure drawing
GET IN TOUCH