8.7/15KV And Below Medium Voltage Special Explosion-Proof Cable

8.7/15KV And Below Medium Voltage Special Explosion-Proof Cable

Production Description

8.7/15kV special explosion-proof cable is composed of conductor, insulation, shock-absorbing filing, ultra-high molecular weight explosion-proof material cladding, explosion-proof armor layer and explosion-proof outer sheath. According to the different needs of customers, the insulation layer is divided into rubber insulation and plastie insulation types. Under the protection of shock-absorbing packing, explosion-proof wrapping, explosion-proof strengthening and explosion-proof armor, the special explosion-proof cable can withstand the shock wave pressure of about 5MPa. At the same time, the antistatic outer sheath can effectively guide the static electricity generated by the friction between the cable and the non-insulator, prevent the fire, explosion and other safety accidents caused by static electricity in military facilities, and perfectly solve the technical problem that the “cable electrostatic bundle” is easy to detonate. Theshock-resistant outer sheath can provide limited protection against the impact damage such as shrapnel cuting caused by the explosion Special explosion-proof cables also solve the curent national defense combat readiness facilities, such as oil depots, chemical storage ammunition depots, hangars, military ports, caverns, military and civil airports, tunnels, military exercise bases, large electric power chemical, coal mines, subway hazardous terminals and other electrical equipment facilities explosion-proof system or unit power transmission security problems.

Executive standard

GB 3936,1-2010 “Explosive atmospheres-Part 1: General requirements for equipment”
Q/WHY 114 “Rated voltage 3.6/6kV~8.7/15kV explosion-proof Power Cable”

Scope of application

Oil storage, chemical storage, Ammunition depots, hangars, military ports, caverns, military and civil airports, tunnels, military exercise bases equipment lines, computer room control lines, trunk, branch distribution system lines, dual power supply control lines.
Oil platform: Power transmission, potentially dangerous explosion area line.
Airport terminal: emergency lighting, fire monitoring system, fire alarm system, emergency elevator, fire telephone, emergency power supply, etc.
Military port: power room transmision limes, fire monitoring system, fire alarm system, smoke emission and ventilation lines kitchen power lines, large power lines, dual power control lines, emergency lighting, emergency broadcast lines, computer room control lines.
Chemical industry: power transmission, general lighting, emergency lighting, potentially dangerous explosion lines and other placesSubway tunnels: power transmission, general lighting, emergency lighting, fire monitoring systems, fire electrical lines, smoke emisiotand ventilation lines.
lron and steel metallurgy: high temperature environment power and control system, emergency power supply, large power linespower supply lines that can not be cut of, power room transmission lines
Power plant: large power lines, general lighting, emergency lighting, fire alarm, fire electrical lines.
Aerospace: Power transmission, general lighting, emergency lighting, computer room control lines, large power lines, high temperature environment power and control lines, potentially hazardous explosion area lines.
Department store: power transmission, general lighting, emergency lighting, emergency broadcast, emergency elevator and lifing equipment lines. library, museum, data processing center fire alarm control lines, fire electrical lines.
Nuclear power plant: power transmission, general lighting, emergency lighting, computer room control lines, large power lines, high temperature environment power and control systems, potentially dangerous explosion area lines.
Places of interest: power transmission, general lighting, emergency lighting, fire alarm, fire electrical lines

Use the feature

Anti-explosion
Under the protection of the reinforced layer, the special explosion-proof cable can withstand the shock wave pressure of about 5MPa. The anti-static outer sheath can effectively guide the static electricity generated by the fiction between the cable and the non-insulator, prevent the safety accidents such as fire and explosion caused by static electricity in military facilities, and the anti-shock wave outer sheath can effectively prevent the impact damage such as shrapnel cutting caused by the explosion
Radiation and electromagnetic interference resistant
This product will not change the resistance value of the insulation material after radiation, which is the ideal distribution cable nuclear facilities. At the same time, the metal braid of the cable forms a natural and optimal shielding layer, which can be used in computer rooms, power dispatching and control rooms where shielding is required.
High mechanical strength
First of all, the special material determines the high mechanical strength, followed by the cable is fattened by external force to theoriginal cable diameter of 2/3, can still maintain the current carrying surface unchanged.

Composition and sequence of product models

Model Voltage grade(kV) Product name Core number & nominal cross section mm²
FB-A-YJU 3.6/6kV Copper core crosslinked polyethylene insulated explosion-proof outer sheath class A explosion-proof cable 1、3core, 25~630
FB-A-YJUG2 Copper core crosslinked polyethylene insulated explosion-proof outer sheath steel tape armouring class A explosion-proof cable
FB-A-YJUG3 Copper core crosslinked polyethylene insulated explosion-proof outer sheath steel wire armouring class A explosion-proof cable
FB-A-YJU 6/6kV、
6/10kV
Copper core crosslinked polyethylene insulated explosion-proof outer sheath class A explosion-proof cable 1、3core, 25~630
FB-A-YJUG2 Copper core crosslinked polyethylene insulated explosion-proof outer sheath steel tape armouring class A explosion-proof cable
FB-A-YJUG3 Copper core crosslinked polyethylene insulated explosion-proof outer sheath steel wire armouring class A explosion-proof cable
FB-A-YJU 8.7/10kV、
8.7/15kV
Copper core crosslinked polyethylene insulated explosion-proof outer sheath class A explosion-proof cable 1、3core, 25~630
FB-A-YJUG2 Copper core crosslinked polyethylene insulated explosion-proof outer sheath steel tape armouring class A explosion-proof cable
FB-A-YJUG3 Copper core crosslinked polyethylene insulated explosion-proof outer sheath steel wire armouring class A explosion-proof cable

Structure Diagram

Explosion-proof performance

After the explosion-proof test, the cable results are shown in the figure below

Explosion-proof cable explosion damage test result table
Cable serial number The first root The second root The third root The fourth root The fifth root The six root
Distance from the center of the explosion /m 2.5 2.3 2.2 2.1 2.0 1.0
Cable Damage Result Good condition Good condition Good condition Good condition Moderate damage Serious damage
Wire core The initial value
The first root
The second root
The third root
The fourth root
The fifth root
The six root
Red, yellow 1000-2500 1000-2500 1000-2500 1000-2500 1000-2500 0 0
Yellow, green 1000-2500 1000-2500 1000-2500 1000-2500 1000-2500 0 0
Red, yellow 1000-2500 1000-2500 1000-2500 1000-2500 1000-2500 0 0

Electrical characteristics

1.20℃ conductor DC resistance in accordance with GB/T3956-2008 standard:
2.20℃ insulation resistance constant is not less than 3670MΩ ·km;
3. The finished cable withstand the power frequency voltage specified in the following table, 5 minutes without breakdown;

Rated Voltage Withstand voltage  kV
3.6/6KV 12.5
6/6KV,6/10KV 21
8.7/10KV,8.7/15KV 30.5

4. Outer sheath surface insulation resistance value is less than 1.0 x 109Ω

Product Standards

Standards Name
Q/WHY114 Explosion-proof power cable with rated voltage 3 .6/6kV~8.7/1 5kV
GB3836.1-2010 Explosive atmospheres – Part 1: General requirements for equipment
IEC364-5-523-1999 Electrical installations in buildings – Current carying capacity of cabling systems
GB/T16895.15-2002 Electrical installations in buildings -Current carying capacity of cabling systems
GB50217-2007 Code for design of electric power engineering cables
AQ3009-2007 Electrical explosion-proof safety code for hazardous places

Design application selection

In the design and application, it is the same as the ordinary cable, the wiring method is simple, the space is small, the laying methodis more diverse, and the maintenance is easy.

Main technical parameters

Omitting …..

RELATED PRODUCTS

GET IN TOUCH

We look forward to serving you! Our team will get back to you promptly.