XLPE insulated & sheathed control cable 450/750V

XLPE insulated & sheathed control cable 450/750V is for transimission line in automatic control or monitoring system, electnical imstrument conmection, etc

Application

This product is applied for transimission line in automatic control or monitoring system, electnical imstrument connection and other occasions of rated voltage up to and including AC 450/750V.

Executive Standard

GB/T 9330-2020

Service Property

1. The rated voltage UU of the cable should be 450/750V.
2. Allowed long-term operating temperature of cable conductor should be 90℃.
3. Cable laying temperature should be not less than 0℃.
4. Recommended allowable bending radius: For non-armored cable should be not less than 8 times outer diameter of the cable, For armored or copper tape shielded structure cable should be not less than 12 times outer diameter of the cable.

Type & Description

Type Description
KYJV XLPE insulated PVC sheathed control cable
KYJVP XLPE insulated PVC sheathed copper wire braided shielded control cable
KYJVP2 XLPE insulated PVC sheathed copper tape shielded control cable
KYJVP3 X PE insulated PVC sheathed aluminum polyester composite film wrapped shielded control cable
KYJV22 XPE insulated PVC sheathed steel tape armored control cable
KYJVP2-22 XLPE insulated PVC sheathed copper tape shielded steel tape armored control cable
KYJV32 XLPE insulated PVC sheathed thin steel wire anored control cable
KYJY XLPE insulated polyolefin sheathed control cable
KYJYP XLPE insulated polyolefn sheathed copper wire braided shielded control cable
KYJYP2 XLPE insulated polyolefn sheathed copper tape shielded control cable
KYJYP3 XLPE insulated polyolefin sheathed aluminum polyester composite film wrapped shielded control cable
KYJY23 XLPE insulated polyolefin sheathed steel tape armored control cable
KYJYP2-23 XLPE insulated polyolefn sheathed copper tape shielded steel tape armored control cable
KYJY33 XLPE insulated polyolefin sheathed steel wire armored control cable

Code & Meaning

Item Code Description
Series coding K Control cable
Buming characteristic Non flame retardant
ZA(B,C) Flame retardant grade A(B,C)
N Fire resistant
DDZ Low smoke low halogen flame retardant
WDZ Low smoke halogen free flame retardant
WDZN Low smoke halogen free flame retardant fire resistant
Conductor Class1 and 2 copper conductor
R Class 5 copper conductor
Insulation YJ XPE insulation
Sheath or inner sheath V PVC sheath
Y Polyolefin sheath
Shield P Copper wire braided shield
P2 Copper tape wrapped shield
P3 Alminum polyester composite film wrapped shielded
Armor 2 Steel tape armor
3 Steel wire armor
Outer sheath 2 PVC sheath, NBR sheath
3 Polyolefin sheath

Main technical index

1. Conductor D.Cresistance at 20℃ complies with stipulations of GB/T3956.
2. Insulation resistance constant should be not less than 36.7MΩ .km.
3. Cable withstand AC 3.0kV for 5 minutes without puncture.